Contact
en
de fr

M-Bus Gateway LTE

CMe2100

C Me2100 LTE 1 freigestellt

Product categories

Water,
Heat / Cooling,
Electricity,
Gas

M-Bus GSM/GPRS Master

Water

Drinking Water

Heat / Cooling

Electricity

Gas

System technology

Wired

M-Bus

Wireless

LTE-4G

Instruments

Smart Building

Your benefits

  • Automated data transmission (push operation) or dial-up connection with subsequent transparent M-Bus readout (pull operation):
    Perfectly equipped for any application
  • Remote configuration or configuration change via SMS or configuration profile from the web server:
    Reduces commissioning costs and configuration errors
  • IR interface for modular extension:
    No need to replace the M-Bus GSM/GPRS Master when connecting additional measuring points, investment protection
  • 100-240 V AC mains power required:
    No extra power supply necessary
  • Operating status display via LED:
    Easy on-site analysis and troubleshooting

Applications

  • Remote supply and remote reading of M-Bus end devices over GSM/GPRS
C Me2100 LTE 1 freigestellt

Properties

  • Built-in M-Bus data centre (memory size app. 1,4 MB) – reading interval of the meter and transmission interval of the M-Bus meter data can be configured
  • M-Bus meter data can be sent to ftp server, web server or as an email
  • Different templates available for the type of meter data transmission
  • Solution for integration of M-Bus meter data into billing systems available (GWFRead Smart)
  • Remote configuration changes and remote ad-hoc-readout can be carried out at any time
  • Device monitoring via digital I/O module (CMeX40, M-Bus-Slave) with option of SMS alarms
  • DIN mounted, modular and expandable - future proof solution
  • Several extension modules (additional M-Bus loads) which are mounted to the right (IR interface) of the module are available
  • M-Bus protocol according to EN 13757-3
  • Transfer rates M-Bus: 300, 2400 Bit/s
  • M-Bus short-circuit protection
  • Operating indicator with LED

Product information

M Bus GSM GPRS Master C Me2100 E Pd40255 DEL 2023 01 12 2
Technical Data
M-Bus GSM/GPRS Master Extension Modules for CMe2100
Mechanics CMe2100 CMeX10 CMeX11 CMeX12S CMeX13S
Dimensions (HxWxD) 90x36x65 mm (2 DIN-Modules 90x36x65 mm (2 DIN-Modules) 90x108x65mm (6 DIN-Modules)
Weight app. 120 g app. 100g app. 220g
Installation Hat rail TS35 (EN 50022) / DIN mounted Hat rail TS35 (EN 50022) / DIN mounted
Casing material Polyamide Polyamide
Protection class IP20 IP20
M-Bus GSM/GPRS Master Extension Modules for CMe2100
Terminals CMe2100 CMeX10 CMeX11 CMeX12S CMeX13S
Power supply L, N screw clamp cable 0,75 - 2,5 mm2 0,5 Nm tightening torque L, N screw clamp cable 0,75 - 2,5 mm2 0,5 Nm tightening torque L, N, Protective Earth screw clamp cable 0,75 - 2,5 mm2 0,5 Nm tightening torque
M-Bus Pin terminal solid wire Ø 0,6 - 0,8 mm Pin terminal solid wire Ø 0,6 - 0,8 mm Pin terminal solid wire Ø 0,6 - 0,8 mm and screw terminal cable 0,25 - 2,5 mm2 0,5 Nm tightening torque
RS232 - - RJ-45
CMe3000 Extension Modules for CMe2100
Electrical CMe3000 CMeX10 CMeX11 CMeX12S CMeX13S
Nominal voltage 100…240VAC / ± 10% / (50/60Hz) 100…240VAC / ± 10% / (50/60Hz)
Power consumption (max.) 2,5 W 3 W 25 W
Power consumption (nom.) 1 W 1,5 mA x M-Bus-Loads + 1 W
Installation category CAT 4 CAT 3
M-Bus GSM/GPRS Master Extension Modules for CMe2100
GSM/GPRS CMe3000 CMeX10 CMeX11 CMeX12S CMeX13S
GPRS class Up to 12 -
Band 850/900/1800/1900 MHz -
M-Bus GSM/GPRS Master Extension Modules for CMe2100
M-Bus specifications CMe3000 CMeX10 CMeX11 CMeX12S CMeX13S
M-Bus standard EN 13757 EN 13757
M-Bus baud rate 300, 2400 Bit/s 300, 2400 Bit/s
Maximum connected M-Bus-Loads (each 1,5 mA) 8 32 56 128 256
Maximum cable length 1000 m1) 1000 m1)
Maximum load capacitance 1.5 μF 1.5 μF
Bus voltage (nom.) 28 V DC 28 V DC 42 V DC
IR Interface for extension modules Yes Yes
Extension possibilities (Additional M-Bus Loads) Yes Maximum of 4 CMe-modules side by side Yes Maximum of 4 CMe-modules side by side
Integration
Transparent M-Bus readout via public fixed IP address TCP -
Transparent M-Bus readout via dial-up connection GSM CSD -
E-Mail SMTP -
FTP Standard FTP client -
HTTP «Standard HTTP and HTTPS client, POST & GET» -
Ambient conditions
Operating temperature range -20 to +55 °C -30 to +55 °C
Storage temperature range -40 to +85 °C -40 to +85 °C
Humidity (non condensing) 80% at temperatures up to 31 °C, decreasing linearly to 50% at 40 °C 80% at temperatures up to 31 °C, decreasing linearly to 50% at 40 °C
Pollution degree 2 2
Approvals
EMV EN 61000-6-2, EN 61000-6-3 EN 61000-6-2, EN 61000-6-3
Safety EN 61010-1, CAT 4 EN 61010-1, CAT 3

1)The maximum possible network reach (entire cable length) as well as the distance to the M-Bus end devices depends greatly on the network topology, the number of connected devices, the cross-section of the used cables and the transfer rate.

Enquire

Last updated: 13.03.2025
Back to the selection