M-Bus data centre / M-Bus remote display / M-Bus level converter

DR 60 / DR 60 FA / DR 60 PW (Discontinued model)

DR 60 DR 60 FA DR 60 PW E Pd40211 01

Product categories

M-Bus data centre / M-Bus remote display / M-Bus level converter

System technology

Your benefits

  • Modular design:
    Can be used as data centre, remote display or level converter
  • M-Bus data centre, remote display or level converter with integrated modem connection:
    Remote meter reading without access to the object
  • Transparent operation:
    Unchanged transfer of read-out data to the communication device
  • Several interfaces (RS232 and RS485) for PC communication:
    Greater distances (up to 1000 m via RS485) possible between M-Bus data centre, remote control or level converter and PC

Applications

  • Remote supply and remote reading of M-Bus end devices
  • On-site read-out of M-Bus meters via keypad and LCD
DR 60 DR 60 FA DR 60 PW E Pd40211 01

Properties

  • M-Bus data centre, remote display or level converter for 60 M-Bus end devices with a standard load of 1,5 mA
  • Can be used as level converter for RS232 and RS485
  • Read-out via keypad and display (except for level converter) or RS232 interface
  • Transfer rates: 300 to 9’600 baud
  • M-Bus protocol according to EN 13757-3
  • Galvanic separation
  • Collision detection
  • Echo cancellation
  • Bit recovery (restoration of the bit times)
  • Continuous short-circuit protection
  • Automatic switch-off for excessive current flow
  • Integrated mains adapter
  • Additional for M-Bus data centre DR 60
  • Periodic storage of meter data possible (interval of between 1 minute and 1 year)
  • 512 KByte flash memory

Product information

Technical Data
Mains adapter
Input 230 V AC 50 Hz
Output 11 W
Housing
Dimensions (WxHxD) 166 x 190 x 112 mm
Protection class IP53 (sealed PG screw connections)
Material PS
Colour Light grey (similar to RAL 7035)
Weight app. 1,3 kg
Ambient conditions
Operating temperature 0 to + 45 °C
Storage temperature -10 to + 60 °C
Humidity (non-condensing) 10 to 70 %
EMC data
Emission DIN EN 50081-1 EN 55022 class B EN 60555
Immunity DIN EN 50082-2 EN 50104 EN 50204 EN 61000-4-4
Terminals
M-Bus (+), (-) 3 terminal pairs
RS485 S+, S- Terminal pair for RS485 interface
RS232 GND, TX, RX Terminals for RS232 interface (PC)
230 V N, L, E Terminals for voltage supply 230 V AC
M-Bus specifications
Execution DR 60 / DR 60 FA / DR 60 PW
Parameter min. typ. max.
Max. no. of connectable devices (load unit 1,5 mA each) - - 60
Internal resistance Ohm - - 15
Display alarm current mA 90 100 110
Excessive current switch-off mA 130 140 160
Bus voltage MARK (normal operating current) V 38,5 39 39,5
Bus voltage SPACE (normal operating current) V 12 12,5 13
Bit threshold end device > centre mA - 7 -
Collision threshold mA - 30 -