DIN rail meter

Eco CountSL

Eco Count SL 85 seitlich 2

Product categories

Electricity

Multifunctional 3-phase energy and power meter with tariff control and compact design for DIN rail mounting

Electricity

Wired

M-Bus

Smart Building

Your benefits

  • Proven measurement method:
    Energy meter for maximum performance with high measurement stability and durability
  • Large graphic LCD display with LED backlighting:
    Easy reading of measured values and settings with excellent visibility of the digits
  • Flexibly configurable:
    Transducer ratio, pulse output

Applications

  • Measurement of electrical energy in industry, ventilation, and heating systems
  • Cost center accounting
  • Building management systems
  • Power monitoring and energy management
Eco Count SL 85 seitlich 2

Downloads

Properties

  • Operating voltage 3 x 230/400 V AC, 50 Hz
  • Direct measurement version or current transformer version
    - Direct connection up to 85 A
    - 1 or 5 A current transformer connection
  • S0 pulse output for active energy
  • 8-digit display with three decimal places 00000.000 kWh
  • Accuracy class B (+/-1%) for active energy EN 50470-1, -3
  • Control input for tariff switching (HT/NT)
  • Display data: active, apparent, and reactive power, power factor, voltage, mains frequency, current (total and per phase)
  • Bidirectional meter (bidirectional)
  • Alarm function with configurable threshold values
  • DIN rail mounting
  • Housing: IP20, dimensions (LxWxD) 90x90x60 mm, installation width 4 TE
  • M-Bus interface according to EN 13757-2, -3
  • Conformity according to MID module D for billing purposes ex works

Product information

Technical Data
Electrical
Measurement accuracy Active energy: Reactive energy: Class B (1%) according to EN50470-3 Class 2 (2%) according to EN62053
Operating voltage Three-phase 3x400/230 V AC +/-10%
Maximum current Direct-reading meters: Transformer meters: 85 A 6 A
Start-up current Direct-reading meters: Transformer meters: <2 mA <2 mA
Internal power consumption Voltage path: Current path transformer meters: 0.6 VA / 0.5W per phase 0.6 VA / 0.5W per phase
Mains frequency Nominal frequency 50 Hz +/-2%
Tariff switching Switchover voltage 230 V AC
Data retention voltage-free in EEPROM, minimum 10 years
Current and voltage connection
Current path – connection cross-section 2.5–25 mm2
Recommended torque 0.4 Nm
Transducer meter: Connection crosssection Recommended torque 0.5–6 mm2 0.4 Nm
Backup fuse Direct-reading meters max. 85 A Transformer meters max. 6 A
Adjustable transformer ratios
Current transformer 5/1 A 1 to 6‘000
S0 pulse output
Standard EN62053-31
Switching voltage/current Switching voltage/current Max. 32V AC/DC, max. 100 mA
Output Potential-free
Pulse rate per kWh/kvarh Direct-measurement meter: 1,000 pulses/kWh or pulses/kvarh Transformer meter: 10,000 pulses/kWh or pulses/kvarh
Pulse length 30 ms
Standard assignment Active energy import
Adjustable pulse output
Instead of active energy pulse output, an alarm output with threshold value detection Active power PSUM, threshold value exceeded Active power PL1, threshold value exceeded Active power PL2, threshold value exceeded Active power PL3, threshold value exceeded Total current ISUM, threshold value exceeded Current IL1, threshold value exceeded Current IL2, threshold value exceeded Current IL3, threshold value exceeded Active power P+, consumption Active power P-, supply Failure on one of the three phases Current IN, threshold value exceeded (direct measurement version only)
Display
LCD display 8 digits with three decimal places 99999.999 Shifts with increasing consumption until 99999999 is displayed
Details LCD display with blue backlighting
Dimensions (WxH) 40x30 mm
2 red LEDs Optical test outputs of the active energy and reactive energy measuring units
M-Bus
Standard EN13757-2, -3
Connection cross-section 0.25–1.5 mm2
Secondary address 8 digits 00000000–99999999 (identical to meter manufacturer number)
Primary address 0 to 250 (default 0)
Baud rate 300, 600, 1,200, 2,400, 4,800, and 9,600 baud (default 2,400 baud)
Configuration Configurable via buttons and software
Environmental
Operating -25 °C to + 55 °C
Temperature limit range -40 °C to + 70 °C
Relative humidity Condensation of moisture on the device must be prevented.
Approvals
MID module D for billing purposes ex works
Dimensions and weights
Dimensions (WxHxD) 90x72x62 mm
Mount 35 mm top-hat rail (DIN 60715:2018-07), position independent
Protection II
Protection type Housing IP20
Material Polycarbonate/acrylonitrile butadiene styrene (PC/ABS)
Weight Direct-reading meter: approx. 260 g Transducer meter: approx. 195 g
Display data
Total 3-phase Per phase Per tariff
Active energy import (kWh)
Active power (kW)
Apparent power (VA)
Reactive power (var)
Power factor
Voltage (V)
Current (A)
Frequency (Hz)
Safety instructions (transformer meter)

Current transformers must not be operated openly, as high voltages may occur. These can cause personal injury and property damage. In order to achieve the protection against dust and water ingress required by the standard (IP 51, EN 50470-1, section 5.9), the devices may only be used in meter cabinets.

Transformer ratio

The transformer ratio can only be set once after installation on calibrated/MID conformity-assessed meters. The meter must then be locked and sealed.