M-Bus pulse collector

IM 2

Variable M Bus Systeme Impulssammler IM2

Product categories

Water

Water

Drinking Water

System technology

Smart City

Smart Building

Your benefits

  • Interface conversion from pulse to M-Bus:
    System change without meter removal
  • Power supply via the M-Bus or integrated battery:
    No mains adapter required, thus saving time and costs per measuring point
  • Regular storage of meter readings in the EEPROM:
    No data loss

Applications

  • IM 2 enables the integration of two consumption meters, each with one pulse output, into the M-Bus data chain
Variable M Bus Systeme Impulssammler IM2

Properties

  • 2-way M-Bus pulse collector
  • Fixed date function – implemented clock with calendar function
  • Parameters of both pulse inputs freely configurable
  • Parameterisation via M-Bus with read only function
  • M-Bus protocol according to EN 1434-3
  • Automatic Baud rate detection (300 or 2400 baud)
  • Supports primary and secondary addressing
  • Full functionality in case of M-Bus failure (battery operation)
  • Simple wall mounting
Supply
Remote supply from the M-Bus with automatic changeover to battery operation in case of Bus failure
Bus operation Max. 1.5mA (1 M-Bus standard load)
Battery operation app. 50µA at 25°C
Battery Lithium 3V, button cell, 230mAh, can be replaced
Battery service life without other supply app. 1/2 year at 25°C
Permissible no. of days with battery operation per year during 10 years of operation app. 18 days at 25°C
M-Bus protocol
Reference standard EN 1434-3
Transfer rate 300 or 2400 Baud with automatic detection
Addressing Primary and secondary addressing
Supports telegrams SND_NKE, REQ_UD2, SND_UD
Data structure: Variable structure, Low-Byte-First (identifier 72h) Length = 53 B 1. Data record: Meter reading 2. Data record: Time and date 3. Data record: Last fixed date 4. Data record: Last fixed date value 5. Data record: Next fixed date 6. Data record: Company-specific attachment
Pulse contact requirements
Potential Potential-free, insulation to earth ›1MΩ
Resistance Open ›1MΩ, closed ‹2kΩ
Maximum capacity (incl. cable) 2nF (short power feed), 12nF (long power feed)
Minimum contact duration 30ms
Minimum interval between 2 pulses 30ms
Maximum pulse frequency 14Hz
Contact voltage 2,5V to 3,6V
Contact current 30µA
Guaranteed debouncing time 5ms
Connection cable Max. 10m (twisted pair recommended)

Technical Data


Housing
Dimensions 80x80x52mm
Installation Wall-mounted
Material Polystyrene
Colour Light grey
Protection class IP54
Pulse inputs 2, parameters individually configurable
Ambient conditions
Operating temperature 0 to +55°C
Storage temperature -20 to +70°C
Humidity (non-condensing) 10 to 70%