Thermal energy meter

Q-Heat 5.5 US (USA)

Q Heat 5 5 qp1 5 Left 45 View

Product categories

Heat / Cooling

The ultrasonic heat meter is one of the flattest devices on the market and, thanks to its removable calculator, can be easily installed even in particularly inaccessible places. The ultrasonic meter can be installed variably as a heat, cold or combination meter. The current consumption, the due date and the due date value can be conveniently recorded with just the push of a button via a display loop.

Heat / Cooling

Ultrasonic

Wired

M-Bus

Wireless

LoRaWAN

Smart Building

Your benefits

  • Ultrasonic technology:
    Long-term stable energy measurement with highest measurement accuracy
  • Compact design:
    Little installation space required on site
  • Flexible installation:
    - Change of flow and return flow
    - Change of the energy unit
    - Removable calculator (compact/split)
  • Large measuring range:
    up for detection of smallest flow rates
  • User-friendly:
    Parameter setting directly via the device buttons
  • Operational reliability:
    Display of operating faults

Applications

  • High-end device in the building technology sector
  • Replacement of mechanical impeller heat meters
  • Heat and/or cold consumption measurement in the building technology sector

Options

  • Measurement Canada-compliant ultrasonic compact heat meter
  • Standard Version with M-Bus interface (powered by battery)
  • Retrofittable with external LoRaWAN radio module (RCM-H200 FW-V ≥1.9.18)
Q Heat 5 5 qp1 5 Left 45 View

Properties

  • Ultrasonic heat and cold meters (combi meter)
  • Nominal diameter ½" to 1½"
  • Nominal flow qp 6.6 - 44 gpm
  • Battery life up to 15 years (depending on environment and configuration
    conditions)
  • Maximum operating pressure 232 psi
  • Temperature range 41°F – 194°F
  • Compact design and removable calculator as standard for tight and difficult to access installation situations
  • Any installation position without restrictions, even "overhead"
  • LCD-Resolution 8 digits
  • Display in kWh, MWh, MJ, GJ possible
  • Temperature sensor pt 1000

Product information

Technical data
Ambient conditions
Protection rating Calculator unit: IP65 according to EN 60529 Flow sensor: IP65 according to EN 60529
Transport -13°F ... 158°F, <95% r.h. (without condensation)
Storage 23°F ... 113°F, <95% r.h. (without condensation)
Usage +41°F ... 131°F, <95% r.h. (without condensation)
Medium Only use water without chemical additives as the medium for this device. Glycol additives or sodium chloride NaCl (common salt) are expressly not permitted!
Standards
Iterference resistance and interference emission EN 301 489-1, EN 301 489-3
Security EN 62368-1 , EN 62479
Quality of the heating medium according to VDI guideline 2035, AGFW standard 510
Influencing quantities
Electromagnetic class E1
Mechanical class M2
Ambient class A
Measuring accuracy class 2
Calculator unit Temperature range
Temperature rage 32°F ... 221°F
Temperature difference range 3K ... 70K
Start of metering temperature difference 0.2K
Power supply
Lithium battery Nominal voltage 3.0 V
Lithium content 0.02046 oz
Battery type CR AA
Batteries per device 1 (replaceable)
Battery life Up to 15 years (depending on environment and configuration conditions)
Display-levels
Display 8-digit LCD + pictograms
Energy display (switchable) Default (kWh) kWh <-> MWh MJ <-> GJ kWh <-> MJ (only up to 13.2 gal (50 liters) of cumulative flow) MWh <-> GJ (only up to 13.2 gal (50 liters) of cumulative flow)
Connecting cable Calculator - volume measuring unit 31.5"
Technical data communication
Connection cable OUT
Function M-Bus
Length 118.11"
Within Scope of delivery included
Protection class IP65
Cable ends End sleeves
Cable sheathing PVC
Connection cable - Colour assignment
M-Bus red black orange (not assigned) brown (not assigned)
M-Bus to RCM-H200 connection red -> brown (ECO+) black -> white (ECO-) orange -> green (ECO Modem) Brown -> (not assigned)
Q heat 5 5 Electrical Schematic 3
Specifications M-Bus
Possible readouts per day 96 (every 15 minutes) 2
Baud rate 300, 2400 (default)

2 if readings are taken less frequently, unused “credits” are stored in the device

Technical data temperature sensor
Temperature sensor
Measuring element Pt1000 according to EN 60751
Type Typ DS
Diameter Ø AGFW - ¼"
Installation variant qp6.6-11 qp15.4-44 AGFW 1.08" – direct installation Asymmetric ¼" - indirect symmetrical (immersion sleeve)
Cable length Default: 59.05" Optional: 118.11"
Technical data flow sensor
Flow sensor
Nominal flow qp gpm 6.6 11 15.4 26.4 44
Nominal diameter DN inch 0.59 0.79 0.98 0.98 1.57
Overall length inch 4.33 5.11 10.24 10.24 11.81
Connection inch G¾B G1B G1¼B G1¼B G2B
Weight lb 1.16 1.46 2.59 2.59 3.86
Installation location Return or forward flow (switchable up to 13.2 gal (50 litres) cumulative flow)
Installation position any
Inlet and outlet section not required (no downstream or upstream straight pipe requirement)
Minimum flow qi gpm 0.07 0.11 0.12 0.21 0.44
Maximum flow qs gpm 13.2 22 30.8 52.8 88.1
Start-up limit q0 gpm 0.026 0.044 0.062 0.106 0.22
Dynamic range 1:100 1:100 1:125 1:125 1:100
Accuracy class 2
Pressure loss at qp psi 1.89 2.61 0.55 1.77 2.44
Max. permissible operating pressure psi 232
Min. system pressure to avoid cavitation psi 21.8 29 14.5 21.8 21.8
temperature range °F 41 ... 194
Dimensional drawings
Masszeichnung Q heat 5 5 1
Masszeichnung Q heat 5 5 2
Dimensions
Nominal flow qp gpm 6.6 11 15.4 26.4 44
1 Pipe length inch 4.33 5.11 10.24 10.24 11.81
2 Threads inch G¾B G1B G1¼B G1¼B G2B
3 Calculator width inch 3.07
4 Calculator length inch 3.98
5 Total height inch 2.56 2.68 3.31 3.31 3.94
6 Height of volume measuring part inch 1.61 1.77 2.36 2.36 2.99