sonico® EDGE

Modbus Module

Screenshot 2023 11 22 151150 Photo Room png Photo Room 1

Produkt Kategorien

Wasser

Wasser

Trinkwasser

Ultrasonic

Systemtechnik

Wired

Modbus

Smart Infrastructure

Smart City

Smart Industry

Ihre Vorteile

  • Detailed volume and flow rate information:
    Cumulative, forward, and reverse volume incl. information about actual flow rate
  • Temperature information:
    Precise water and environmental temperature
    measurements
  • Alarm status and version information:
    Alarm status of the flow meter and information about actual firmware version
    installed.
  • High flexibility:
    Multiple communication modules attached to the meter can operate simultaneously.
  • Water proof design:
    Sealed housing (IP68)
  • Plug & Play:
    Easy and fast on-site installation with auto NFC interface-detection

Einsatzgebiete

  • Industrial application
  • Building management system
  • Data logging in combination with various data loggers
  • Installation in harsh and flooded environment
Screenshot 2023 11 22 151150 Photo Room png Photo Room 1

Eigenschaften

  • Modbus RTU/ASCII protocol with extended flowmeter data
  • Compatible with sonico EDGE flowmeter
  • DC powered over Modbus cable
  • Simple installation and automatic start-up after connecting to meter.
  • Continuous and tamper-proof connection, thoroughly reliable results
  • Can be factory fitted or retrofitted at installation site without breaking metrological seal.
  • Snap-in NFC module slots – no connectors or cables needed.
  • Approval

Dimensions (mm)


Dimension Module
Sonico Modbus Module EP10310 1 1 1 2 1 3

Technical data


General
Operating temperature -25 to + 70 °C
Storage temperature -25° to 70°C (dry environment)
Weight potted Module with cable 290 g
Electrical data
Voltage supply + 12 VDC to + 24 VDC (+/- 10%)
Standby current 4 mA
Operating current <30 mA
Relative humidity 0 to 90 % (IP68)
Min. req. FW version Sonico EDGE COM 2.XX
Bus termination Line termination 120 ohm
Cable connection
Cable Twisted pair RS-485 (2x2x0.25 shielded)
Length 3m
Max. allowed cable length (default installation conditions) 30m
RS-485 cable interface Terminal A, B and shield (Ground or PE)

Protocol information


Protocol value
Value Corresponding Protocol
7 ASCII
8 RTU (default)
Parity
Value Corresponding Parity
0 None (default)
Stop Bit
Value Corresponding Stop bit
1 1 (default)
2 2
Baud rate [BPS] (The Protocol value defines the data bits.)
Value Corresponding Baud rate
1 600
2 1200
3 2400
4 4800
5 9600
6 19200 (default)
7 34800
8 57600
9 115200
Holding Register (Big Endian Encoding)

Read Holding Register = Function Code 3
Write Single Register = Function Code 6

Address Size [bit] Access [R/W] FCN Code Values / parameters / Description
Address 16 R 3 Module readout with fixed hex value: - Default value 0x1EE6 for GWF Manufacturer ID
1001 16 R 3 Module readout with fixed unsigned value, FW Version = readout value / 100 Firmware Version
1002 16 R 3 Module readout with fixed unsigned value type 7 Device Type
1003 16 R 3 Meter readout with fixed unsigned value Volume Unit
1004 16 R 3 Meter readout with fixed unsigned value Volume Decimals
1005 16 R 3 Meter readout with fixed unsigned value Flow Unit
1006 16 R 3 Meter readout with fixed unsigned value Flow Decimals
1007 16 R 3 Meter readout with fixed unsigned value: - Operation = 2 - Testbench = 3 Meter Mode
1008 16 R 3 Meter readout with fixed unsigned value: - No flow direction set = 0 - Arrow direction from right to left = 1 - Arrow direction from left to right = 2 Flow Direction
1009 16 R 3 Meter readout with fixed unsigned value - Meter 24 VDC powered = 0 - Meter Battery powered = 1 Battery Symbol
1010 4x16 R 3 64-bit Meter value readout: - In Operation Mode = 2 with 3 decimals - In Testbench Mode = 3 with 4 decimals Cumulative Volume
1014 4x16 R 3 64-bit Meter value readout, no decimals Volume Flow
1018 4x16 R 3 64-bit Meter value readout: - In Operation Mode = 2 with 3 decimals - In Testbench Mode = 3 with 4 decimals Forward Volume
1022 4x16 R 3 64-bit Meter value readout: - In Operation Mode = 2 with 3 decimals - In Testbench Mode = 3 with 4 decimals Reverse Volume
1026 16 R 3 Air Temperature = Edge value readout/100 Air Temperature
1027 16 R 3 Water Temperature = Edge value readout/100 Water Temperature
1028 16 R 3 Meter hex value readout: - No error 0x00 - Module not physically attached on an Edge 0x30 - Module physically attached on an Edge but Edge not responding at all 0xB0 - Wrong messages received 0x50 - Any Edge Alarm - Alarm Bank 1-2 0x13 Module Status
1029 16 R 3 Meter hex value readout: - Air in pipe 0x0001 - Reverse flow 0x0004 - Leak detection 0x0008 - Burst pipe 0x0010 - No usage 0x0020 - Water temperature 0x0080 - Electronics temperature 0x0100 - No external power supply 0x2000 - Internal error (Any MET alarm) 0x8000 Alarm 1
1030 16 R 3 Meter hex value readout: - AES encryption 0x0001 Alarm 2
1031 2x16 R 3 Edge SN readout with max. 8 numeric characters EDGE Serial Number
2000 16 R/W 3/6 Set C: Stop Bits, B: Parity and AA: Baud Rate according UART Data Setup: 0xCBAA, default 19200, 8, n, 1 UART Setup
2001 16 R/W 3/6 1 to 247, default address 1 Reserved Addresses (do not use): - Broadcast 0 - Modbus specific 248-255 Modbus Address
2002 16 R/W 3/6 0 = ASCII 1 = RTU, default (1 = RTU) Modbus Protocol
2003 16 W 6 KEY: 12345 Safe & Reboot

SCHEME & STANDARDS


Modbus Datasheet Schematic

Standards


EC 61000-4-5 1.2/50-μs surge ±4,000 [kV]
IEC 61000-4-2 Contact discharge ±15,000 [kV]
IEC 61000-4-2 Air-gap discharge ±15,000 [kV]
IEC 61000-4-4 Electrical fast transient ±4,000 [kV]

Anfrage

Last updated: 07.03.2024