GWFcoder® -Interface

M-Bus / M-Bus / SCR MP

Zaehlerfernauslesung GW Fcoder Interface M Bus M Bus SCR IEC

Kategorie produktowe

Woda,
Ciepłomierze / Chłodomierze,
Gaz

Remote meter reading

Woda

Woda pitna

Ciepłomierze / Chłodomierze

Gaz

Smart City

Korzyści

  • Interface multiplication:
    Multiple use of meter data
  • Use of a GWFcoder® meter with SCR (IEC) interface in an M-Bus network:
    Meter data can be made available to the end customer
  • Labeled connection terminals:
    Easy on-site installation

Zastosowanie

  • With the interface, water and gas meters equipped with GWFcoder® registers can be read by the utility for billing purposes and by the building management system for energy optimization.
Zaehlerfernauslesung GW Fcoder Interface M Bus M Bus SCR IEC

Cechy

  • Data compatibility – for the M-Bus master, the interface behaves like a GWFcoder® meter with integrated M-Bus
  • Polarity-independent connection of GWFcoder® meters to the interface
  • DIN rail mounting
  • With the interface, a GWFcoder® meter with SCR (IEC) interface can be integrated simultaneously into two separate M-Bus networks. The interface automatically reads the GWFcoder® register at predefined intervals and stores the current data set in the internal memory.
    When a readout via M-Bus is performed, the data are immediately available and transmitted to the master.

Product information

Components
E Pe40234 components
General Operating Behavior
  • The start-up time after power ON is max. 15 seconds. The interface automatically reads the data from the GWFcoder® register.
  • After successful readout of the GWFcoder® register, the interface can be selected and read out by the M-Bus master.
  • The readout software must support interpretation of the GWFcoder® data record. The data record is compatible with the data record of GWFcoder® meters with integrated M-Bus. This data record is already supported by most providers.
Readout Interval
  • The meter reading is updated in the interface after each readout and additionally every 15 minutes.
  • If the meters are read cyclically within the M-Bus network, a pause of at least 15 seconds must be observed at the end of each cycle.
  • The readout interval of the interface must not be less than 15 seconds.
Commissioning
  • During commissioning, the baud rate for “M-Bus a” and “M-Bus b” must be verified and, when using primary addressing, the address must be parameterized. The secondary address is read directly by the interface from the GWFcoder® register.
  • “M-Bus a” must be connected, as the interface is powered via this connection.
  • After replacing a meter, “M-Bus a” must be restarted (power OFF/ON), and the meter list of both M-Bus networks must be updated in the readout software.
  • After replacing the interface, the baud rate and, if applicable, the primary address must be reconfigured.
Technical Data
Data Transmission – M-Bus
Baud rate M-Bus a 2400 Baud (Standard) or 300 Baud
Baud rate M-Bus b 2400 Baud (Standard) or 300 Baud
Primary address M-Bus a 1–250
Primary address M-Bus b 1–250
Secondary address GWFcoder® meter number – 8 digits, numeric
M-Bus Load
Load M-Bus a: 5 M-Bus unit loads (7.5 mA – supply)
Load M-Bus b: 2 M-Bus unit loads (3 mA – supply)
Installation
The interface can be installed at the M-Bus master or at the meter.
Maximum Cable Length
SCR connection cable 150 m
M-Bus connection cable Depending on network configuration
Dimensions and Weight
Dimensions 25x78x47 mm
Weight approx. 50 g
Operating Conditions
Temperature -10 bis +60 °C
Protection class IP40
Interfaces
M-Bus according to EN 13757
Inductive via SCR / protocol IEC 62056-21
Mounting Type
DIN rail mounting
Supported Meters
GWFcoder® cold water and gas meters with SCR (IEC) interface
Meter Connection Scheme
Meter Type Connection Wires
MTKcoder® IP67 Without approval, CE conformity (MID) white, brown
MTKcoder® IP68 Without approval, CE conformity (MID) black, red (cut green wire)
MTKcoder® MP IP67 CE conformity (MID) white, brown
MTKcoder® MP IP68 CE conformity (MID) black, red (cut green wire)
WPDKcoder WSDKcoder Meitwin mit GWFcoder® WPVD mit GWFcoder® Ohne Zulassung black, red (cut brown wire)
Meistream mit GWFcoder® Meistream Plus mit GWFcoder® Meitwin mit GWFcoder® WPV-MS mit GWFcoder® CE conformity (MID) white, brown
Meistream mit GWFcoder® MP Meistream Plus mit GWFcoder® MP Meitwin mit GWFcoder® MP WPV-MS mit GWFcoder® MP CE conformity (MID) black, red (cut green wire)
Interface M Bus M Bus SCR MP IEC E Pd40234 3
Connection and Signal Transmission / Interface
M-Bus a +/- M-Bus master according to EN 13757-2, supervisory system After power ON, the interface requires 15 seconds to become operational. Power supply via “M-Bus a”.
M-Bus b +/- M-Bus master according to EN 13757-2, supervisory system After power ON, the interface requires 15 seconds to become operational.
Ea GWFcoder® register (polarity-independent)