Pulse generator for UNICO®, MTK, MTW & MTH

Pulse generator IPG 14

Hauswasserzaehler Impulsgeber IPG14

Product categories

Water

Pulse generator for UNICO®, MTK, MTW and MTH

Water

Drinking Water

System technology

Wired

Impulse

Smart City

Smart Building

Your benefits

  • Determination of continuous flow rate:
    Reliable process control
  • Integrated protective resistance:
    Protection against overload

Applications

  • The pulse generator IPG14 found in GWF volume measuring parts is a component of heat meters and GWF water meters for remote indication, pulse collectors, pulse processing systems / long term pulse acquisition systems and frequency converters.
Hauswasserzaehler Impulsgeber IPG14

Properties

  • Low frequency pulse generator
  • Potential free Reed contact
  • Variety of pulse values available
  • High switching cycle number
  • Protection class IP67

Technical data


Switching element Reed
Switching voltage Umax max. 42 V AC/DC
Switching current Imax 100 mA
Switching capacity Pmax 4 W
Resistor R 18 Ohm
Conductor cross section 0,14 mm2
Switching cycles app. 107
Meter Cable length Isolation Thermal limits
UNICO® 1,5 m / 3 m PVC grey max. 90 °C
MTK, MTW 1,5 m, 3 m, 5 m PVC grey / TPE grey max. 90 °C /max. 130 °C
MTH 1,5 m, 5 m TPE grey max. 130 °C
Pulse value table

Meter type Size: qp/Qn Size: Q3 Pulse value (1 Pulse = …liter)
UNICO® 0,6-1,5 1-2,5 - 0,25 1 2,5 10 25
UNICO® 2,5 4 1 2.5 10 25 100 250
MTK, MTW, MTH 1,5-6 2,5-10 11) 2,5 10 25 100 250
MTK, MTW, MTH 10-15 16-25 - 2,5 10 25 100 250

1)Nur Messbereich 1:25 / R40 verfügbar

Application


E Pe40217 application

Connection scheme


E Pe40217 connection sheme

Installation – Recommendations


Continuous contact

The Reed switch emits pulses of varying length depending on the water meter flow rate. Continuous contact can also occur when the roller counter is standing still. Connected devices must be able to withstand continuous contact or protective measures must be provided (wiping contact).
 

Long cable distances

For cable distances greater than 100 m without signal amplifier, we recommend the use of shielded and twisted cables.

See cable recommendations for electricians - BAe20603

Pulse transmission interference

In case of interference during the pulse transmission between the pulse generator and the pulse receiver, (i.e. cable is in the same duct as power cable), we recommend shielded and twisted cables.