Ultrasonic volume measuring device

ULTRAFLOW® 85

UF85

Product categories

Heat / Cooling

ULTRAFLOW® 85 is a static flow sensor based on the ultrasonic measuring principle and has been designed for use in heat and cooling installations where water is used as the heat-bearing medium. It is used primarily as a subassembly of a thermal energy meter in combination with a set of Temperaturesensor and the separate calculators MULTICAL® 603/803. Especially suitable for district heating/cooling applications (main meters, transfer stations, etc.) in billing transactions.

Heat / Cooling

Ultrasonic

Smart City

Smart Building

Your benefits

  • Durable, wear-free ultrasonic volume measuring unit:
    High measuring stability and operational reliability
  • Compact design:
    Little installation space required on site
  • High resolution of the pulse value:
    Precise instantaneous values
  • CH refrigeration approval (METAS) incl. initial calibration:
    Approved for use in clearing traffic

Applications

  • Especially suitable for district heating/cooling applications (main meters, transfer stations, etc.) in billing traffic
  • Heating and/or cooling consumption measurement in the building services sector
  • MID-approved bidirectional flow measurement

Options

  • Pulse transmitter with its own power supply for cable lengths >10 m
UF85

Properties

  • Nominal flow rate: qp150 - qp1000 m³/h
  • Nominal diameter: DN150 to DN300
  • Low pressure loss
  • Built-in display
  • Medium temperature: 2 to 130 °C
  • Type testing/approval:
    - Heat: Conformity in accordance with the European Measuring Instruments Directive (MID B+D)
    - Cooling: CH approval (METAS) incl. initial calibration

Product information

Compliance
Type approval

ULTRAFLOW® 85 is approved as a heat meter in accordance with MID 2014/32/EU:
EU-Type Examination certificate DK-0200-MI004-048
MID-certified according to Module D DK-0200-MID-D-001
ULTRAFLOW® 85 is approved as a cooling meter in accordance with DK-BEK 1178 – 06/11/2014:
System designation TS 27.02 019
Verification DANAK accreditation 268
Standards and documents
EN EN 1434:2022
OIML OIML R75:2002
WELMEC WELMEC 7.2:2023 (May 2024)
CE-marking
ULTRAFLOW® 85 is marked in accordance with
EMC-directive 2014/30/EU
LV-directive 2014/35/EU (together with Pulse Transmitter or Pulse Divider)
PE-directive 2014/68/EU (category I or II)
Approved meter data
MID designation:
Mechanical environment M1 (vibrations and shocks of low significance) M2 (significant or high levels of vibrations and shocks)
Electromagnetic environment E1 (residential, commercial and light industrial buildings) E2 (other industrial buildings
Electromagnetic environment 5…55 °C, condensing, closed location (indoors installation)
Accuracy class 2 and 3
EN 1434 designation:
Environmental class C (high electrical and electromagnetic conditions)
Fast response meter Volume sampling interval (sub-assembly flow sensor) depends on connected calculator. Down to 0.5 s with MULTICAL® 603-S/603-U/803-A. Requires mains supply. Otherwise 1 s.
Technical Data
Electrical data
Internal supply voltage Battery: 3.6 VDC ± 0.1 VDC
- Display backlight OFF
- (MULTICAL® or Pulse Transmitter/Pulse Divider) 3.65 VDC, D-cell lithium
Battery lifetime: (replacement interval)
- ULTRAFLOW® 85 and MULTICAL® serial mode pulse mode Up to 16 years @ tBAT <30 °C Up to 13 years @ tBAT <30 °C
- Pulse Transmitter/Pulse Divider 6 years @ tBAT <30 °C (Y=3)
Mains supply:
- Display backlight ON
- MULTICAL® or 230 VAC +15/-30 %, 50 Hz or 60 Hz
- Pulse Transmitter/Pulse Divider 24 VAC ± 50 %, 50 Hz or 60 Hz
Backup supply Integral capacitor eliminates operational disturbances due to short-term power cuts
Cable length:
- Flow sensor Max 10 m
- Pulse Transmitter/Pulse Divider Depends on calculator – max 100 m when connected to MULTICAL® (Y=2)
- Cable Extender Box Depends on calculator – max 30 m when connected to MULTICAL® (does not provide galvanic separation, but supports measurement of forward and reverse flow as well as extended info codes)
Electromagnetic environment Fulfils EN 1434 class C, MID E1 and E2
Pulse output: Galvanically connected (ULTRAFLOW®)
- Typ Push-Pull
- Output impedance 10 kW
- Pulse duration 2...6 ms
- Pause time Depending on current pulse frequency
Mechanical data
Accuracy class 2 and 3
Electromagnetic environment Fulfils EN 1434 class C, MID E1 and E2
Mechanical environment MID M1 and M2
Ambient conditions 5…55 °C, closed location (installation indoors)
Protection class:
- Flow sensor - Cable extender box - Pulse Transmitter/Pulse Divider IP68 IP68 IP67
Medium in flow sensor Water – recommended water quality as in CEN TR 16911 and AGFW FW510
Medium temperature 1) 2...150 °C or narrower range
Pressure stage PN16, PS16 (DN300) PN25, PS25 or PN16, PS16 (DN150-250); see marking
Straight inlet requirement 0D (according to EN 1434:2022 and OIML R75:2002)
Installation angle Horizontally, vertically and at an angle

1) At medium temperature above 120 °C ULTRAFLOW® 85 must be insulated!
Do not cover the hole of the extension tube, when insulating ULTRAFLOW® 85!

Flow data
Flow Data
Nom. flow qp [m3/h] 150 250 400 600 1000
Meter factor 1) [p/l] 1 0.6 0.4 0.25 0.15
Dynamic range qp:qi 100:1
qs:qp 2:1
Flow@125 Hz 2) [m3/h] 450 750 1125 1800 3000
Min. cut off [l/h] 750 1250 2000 3000 5000

1) The meter factor appears from the type label.
2) Saturation flow 125 Hz. Max. pulse frequency is maintained at higher flow.

Measurement accuracy
Measurement accuracy
Class 3 Ef = ±(3 + 0.05 qp/q), but not above ±5 %
Class 2 Ef = ±(2 + 0.02 qp/q), but not above ±5 %
Typical 1) Ef = ±(1 + 0.01 qp/q)

1) Documented with DANAK-accredited certificate at flow qi, 0.1 qp and qp.

Ultraflow 85 Measurement accuracy diagramm
Materials
Wetted parts
Housing Stainless steel, W.no. 1.4308
Flanges Stainless steel, W.no. 1.4301
Transducer Titanium
Gaskets Fibre
Electronics box
Extension tube Thermoplastic, 40 % glass-reinforced Polyphenylenesulfide (PPS)
Base part Thermoplastic, 10 % glass-reinforced polycarbonate (PC)
Transparent lid Thermoplastic, Polycarbonate (PC)
Top cover Thermoplastic, 10 % glass-reinforced polycarbonate (PC)
Calculator mount bracket Thermoplastic, 10 % glass-reinforced polycarbonate (PC)
Signal cable (optional) Silicone cable (3 x 0.5 mm²)
Power supply cable 24/230 VAC (optional for Pulse Transmitter/Pulse Divider) Cable with PVC mantle (2 x 0.75 mm²)
Housing, Cable Extender Box
Base, cover Thermoplastic, acrylonitrile butadiene styrene (ABS)
Housing, Pulse Transmitter/Pulse Divider
Base, cover Thermoplastic, 10 % glass-reinforced polycarbonate (PC)
Dimensional sketches Ultraflow 85
Flange facing type B, raised face according to EN 1092-1

Ultraflow 85 Drawing
Ultraflow 85 PN16
Nom. Flow qp [m3/h] 150 250 250 400 400 600 600 1000
Nom. Diameter [mm] DN150 DN150 DN200 DN200 DN250 DN250 DN300 DN300
PN, PS [bar] 16
L [mm] 500 600 500
D [mm] 285 340 405 460
k [mm] 240 295 355 410
Bolts Quantity 8 12
Bolts Thread M20 M24
Bolts d2 [mm] 22 26
E [mm] 264 281 341 370
Approx. weight [kg] 27 41 67 80
Ultraflow 85 PN25
Nom. Flow qp [m3/h] 150 250 250 400 400 600
Nom. Diameter [mm] DN150 DN150 DN200 DN200 DN250 DN250
PN, PS [bar] 25
L [mm] 500 600
D [mm] 300 360 425
k [mm] 250 310 370
Bolts Quantity 8 12
Bolts Thread M24 M27
Bolts d2 [mm] 26 31
E [mm] 264 281 341
Approx. weight [kg] 33 53 83
Dimensional sketches Boxes
Pulse Transmitter/Pulse Divider

Ultraflow 85 Pulse Transmitter Divider Box Drawing
Cable Extender Box

Ultraflow 85 Cable Extender Box Drawing
Pressure loss
Designation unit A B C D
Nom. flow qp [m3/h] 150 250 250 400 400 600 600 1000
Nom. diameter [mm] DN150 DN200 DN250 DN300
Length [mm] 500 500 600 500
Δp@qp [bar] 0.02 0.06 0.02 0.04 0.02 0.04 0.01 0.03
kv 1100 1945 2940 5900
q@0.25 bar [m3 /h] 550 973 1470 2950
Ultraflow 85 Pressure loss Diagramm
Installation
attentionTriangle

Please read this chapter carefully before installing the meter

In case of incorrect mounting, Manufacturer's guarantee obligations no longer apply. By connecting to 230 V supply, there is a risk of electric shock. When working on the flow sensor in the installation, there is a risk of outflow of (hot) water under pressure. At a media temperature higher than 60 °C, the flow sensor should be shielded from unintended contact. Prior to installation of the flow sensor, the system should be flushed. Correct flow sensor position (inlet or outlet) appears from the front label of MULTICAL®. The forward flow direction is indicated by an arrow on the flow sensor.

attentionTriangle

ULTRAFLOW® 85 may be lifted in the lifting rings only.

Pressure stage: PN16, PS16 or PN25, PS25. See marking on flange or label 
Temperature of medium: 2…150 °C or narrower range. See marking on label. 
Mechanical environment: M1 and M2 (fixed installation with minimum vibration and fixed installation with considerable or high vibration level respectively). 
Electromagnetic environment: E1 and E2 (housing/light industry and industry respectively). The meter’s signal cables must be drawn at min. 25 cm distance to other installations. 
Ambient conditions: The ambient temperature must be within 5…55 °C. Installation must be in closed locations (indoors). 
Protection class: IP68 – The flow sensor is durable, even in permanently wet conditions. 
Insulation: ULTRAFLOW® 85 can be insulated. At medium temperature above 120 °C ULTRAFLOW® 85 must be insulated.
Maintenance and repair: The flow sensor is verified separately and can, therefore, be separated from the calculator. It is permitted to replace the transparent lid and the 3-wire cable from ULTRAFLOW® 85 on-site. Other repairs must be performed in a workshop and requires subsequent reverification in an accredited laboratory.

Heat installations the tower can point in any direction. icon360Degrees
Cooling installations the tower must always point upwards to avoid risking condensation damaging the electronics. icon180Degrees
Straight inlet ULTRAFLOW® 85

ULTRAFLOW® 85 requires neither straight inlet nor outlet in order to fulfil the Measuring Instruments Directive (MID) 2014/32/EU and EN 1434. Only in case of heavy flow disturbances before the meter will a straight inlet section be necessary. We recommend following the guidelines in CEN TR 13582.

Operating pressure

To minimise the risk of measuring errors as a result of cavitation or air in the water, it is recommended to keep a sufficient static pressure at the flow sensor outlet of min. 1.5 bar at qp and min. 2.5 bar at qs . This applies to temperatures up to approx. 80 °C.

Electrical connection

Connecting via Pulse Transmitter/Pulse Divider/Cable Extender Box

ULTRAFLOW® 85 Pulse Transmitter/Pulse Divider/ Cable Extender Box MULTICAL®
Input Output
Blue (GND) 11 11A/11 11
Red (supply) 9 9A/9 9
Yellow (signal) 10 10A/10 10

Pulse Transmitter/Pulse Divider provides galvanic separation, but does not support extended info codes and bi-directional flow measurement. 

Cable Extender Box does not provide galvanic separation, but supports extended info codes and does not prohibit bi-directional flow measurement. 

If long signal cables are used, please consider the installation carefully. There must be at least 25 cm between the signal cable and all other cables due to EMC.

ULTRAFLOW® 85 is preferentially mains supplied e.g. via MULTICAL® 603-S/-U to achieve e.g. the highest volume sampling frequency

In case of battery supply the battery lifetime depends on many parameters like e.g. data communication, integration mode and environmental temperature. For further information, see the technical documentation of the connected MULTICAL® calculator

ULTRAFLOW® 85 MULTICAL® Designation Color
11 11 GND (Blue)
9 9 +3.6V (Red)
10 10 Signal (Yellow)

Enquire

Last updated: 12.02.2026
Back to the selection