Ultrasonic volume measuring meter

US ECHO II

US ECHO II E Pd20412 1

Product categories

Heat / Cooling

Ultrasonic volume measuring meter for hot water up to 130 °C

Heat / Cooling

Ultrasonic

Smart Building

Your benefits

  • Robust, high grade wear resistant materials:
    Excellent measuring stability and reliability
  • Universal applicable with diverse calculators:
    Meets various requirements also with regard to interfaces
  • Integrated intelligence (status and warning messages):
    Simple and quick on-site troubleshooting

Applications

  • As a replacement for mechanical impeller heat meters
  • Metering of heat and/or cooling consumption in building management

Options

  • Pulser with 5 m or 9 m cable
US ECHO II E Pd20412 1

Properties

  • Nominal diameters from DN 15 up to DN 50
  • Nominal flow rates from qp 0,6 up to qp 15
  • Lower pressure loss
  • No moving parts
  • Maximum operating pressure PN 16 bar (Threaded) / PN 25 bar (Flanged)
  • Temperature up to 130 °C
  • Conformity according to European Measuring Instruments Directive (MID)
  • Pulser with 3 m cable
    (Standard pulse value: DN 15–32: 2,5 liters, DN 40-50: 10 liters)
  • Environmental class C, Accuracy class 2

Product information

Technical Data
E Pe20412 01
Dimension Diagram
US ECHO II E Pd20412 3
Typical Head Loss Curve
E Pe20412 02
Materials
Installation

Body up to DN 20: Brass
Body from DN 25: Bronze

Pipeline: horizontal iconHorizontalLine
vertical iconVerticalLine
Meter head: sideways iconArrowLeftRight
± 45° icon45Degrees
Installation - Recommendation

With the US ECHO II, the electronic housing must be mounted on the side (when installed horizontally). US ECHO II may be turned up to max. ± 45° in relation to the pipe axis. A straight inlet or outlet section is not required for US ECHO II ultrasonic volume measuring meters. However, an inlet section of at least 5 x DN is recommendable if sufficient space is available.

Installation recommendations
The choice of installation site must ensure air cannot collect in the meter.

Technical data Pulse generator
Switching element
Type Passive Open collector
Switching voltage Umax 30 V DC
Switching current Imax 27 mA
Switching capacity Pmax 0,81 W
Pulse length 5 ms
Pulse value table
Installation – Recommendations
Pulse generator DN 15 …32 1 Pulse = ... Liters DN 40/50 1 Pulse = ... Liters
Pulse 2,5 10

Pulse transmission interference
In case of interference during the pulse transmission between the pulse 
generator and the pulse receiver, (i.e. cable is in the same duct as power cable), we recommend shielded and twisted cables.