M-Bus pulse collector

IM 2

Variable M Bus Systeme Impulssammler IM2

Kategorie produktowe

Woda

Woda

Woda pitna

Technika systemowa

Z przewodem

Impulse,

M-Bus

Smart City

Smart Building

Korzyści

  • Interface conversion from pulse to M-Bus:
    System change without meter removal
  • Power supply via the M-Bus or integrated battery:
    No mains adapter required, thus saving time and costs per measuring point
  • Regular storage of meter readings in the EEPROM:
    No data loss

Zastosowanie

  • IM 2 enables the integration of two consumption meters, each with one pulse output, into M-Bus data chain
Variable M Bus Systeme Impulssammler IM2

Cechy

  • 2-way M-Bus pulse collector
  • Fixed date function – implemented clock with calendar function
  • Parameters of both pulse inputs freely configurable
  • Parameterisation via M-Bus with read only function
  • M-Bus protocol according to EN 13757-2 and -3
  • Automatic Baud rate detection (300 or 2400 baud)
  • Supports primary and secondary addressing
  • Full functionality in case of M-Bus failure (battery operation)
  • Simple wall mounting

Product information

Technical Data
Supply
Remote supply from the M-Bus with automatic changeover to battery operation in case of Bus failure
Bus operation Max. 1,5 mA (1 M-Bus standard load)
Battery operation app. 50 µA at 25 °C
Battery Lithium 3 V, button cell, 230 mAh, can be replaced
Battery service life without other supply app. 1/2 year at 25 °C
Permissible no. of days with battery operation per year during 10 years of operation app. 18 days at 25 °C
M-Bus protocol
Reference standard EN 13757-2 and -3
Transfer rate 300 or 2400 Baud with automatic detection
Addressing Primary and secondary addressing
Supports telegrams SND_NKE, REQ_UD2, SND_UD
Data structure: Variable structure, Low-Byte-First (identifier 72 h) Length = 53 B 1. Data record: Meter reading 2. Data record: Time and date 3. Data record: Last fixed date 4. Data record: Last fixed date value 5. Data record: Next fixed date 6. Data record: Company-specific attachment
Pulse contact requirements
Potential Potential-free, insulation to earth ›1 MΩ
Resistance Open ›1 MΩ, closed ‹2 kΩ
Maximum capacity (incl. cable) 2 nF (short power feed), 12 nF (long power feed)
Minimum contact duration 30 ms
Minimum interval between 2 pulses 30 ms
Maximum pulse frequency 14 Hz
Contact voltage 2,5 V to 3,6 V
Contact current 30 µA
Guaranteed debouncing time 5 ms
Connection cable Max. 10 m (twisted pair recommended)
Housing
Dimensions 80 x 80 x 52 mm
Installation Wall-mounted
Material Polystyrene
Colour Light grey
Protection class IP54
Pulse inputs 2, parameters individually configurable
Ambient conditions
Operating temperature 0 to + 55 °C
Storage temperature -20 to + 70 °C
Humidity (non-condensing) 10 to 70 %