For fully filled pipes
KATflow 230
Kategorie produktowe
Mobile Clamp-On ultrasonic flow meter
Woda
Hydroenergia
Ultradźwiękowe
Smart Infrastructure
Korzyści
- Pipe diameter range 10 mm to 3000 mm
- Temperature range for sensors -30 °C to +250 °C (-22 °F to +482 °F)
- Selectable three-line LCD display and full keypad
- Robust IP 65 aluminium enclosure
- Battery life up to 24 hours with easily replaceable battery cartridge
- Measurement of two flows simultaneously
Zastosowanie
- Heating, Ventilation and Air Conditioning (HVAC) measurements
- Large pipe measurement with two sensor pairs in ‘X’ configuration
- Temporary replacement of conventional in-line flowmeters
- Building surveys on large facilities
- Efficiency monitoring of heat exchangers
Opcje
- Pipe wall thickness gauge
- Available with crush-proof IP 67 transport case or lightweight soft case
- Expansion box for additional input or output configuration and special solutions
- Software for data evaluation
- Special waterproof solution available for harsh environmental conditions
Pliki do pobrania
Cechy
- Dual flow monitoring with sum, average, difference and maximum calculations
- PT100 inputs for heat quantity (thermal energy) measurement
- Process output options including current, open-collector, relay
- Large data logger and software for sampling and data transfer
- Stainless steel sensors, cable and connectors as standard
Product information
Flowmeter
Performance
| Measurement principle | Ultrasonic transit-time difference |
| Flow velocity range | 0,01...25 m/s |
| Resolution | 0,25 mm/s |
| Repeatability | 0,15 % of measured value, ±0,015 m/s |
| Accuracy | Volume flow: ±1...3 % of measured value depending on application ±0,5 % of measured value with process calibration Flow velocity: ±0,5 % of measured value |
| Turn down ratio | 1/100 (equivalent to 0,25...25 m/s) |
| Measurement rate | 100 Hz (standard) |
| Response time | 1 s |
| Damping of displayed value | 0...99 s (selectable by user) |
| Gaseous and solid content of liquid media | <10 % of volume |
KATflow 230 (dimensions in mm)
General
| Enclosure type | Portable |
| Degree of protection | IP 65 according to EN 60529 |
| Operating temperature | -10...+ 60 °C (14...+ 140 °F) |
| Housing material | Extruded aluminium, AI MG Si 0.5, lids die-cast zinc alloy, GD-Zn AL 4 CU 1 |
| Measurement channels | 1 or 2 (optional) |
| Calculation functions | Average, difference, sum, maximum (dual-channel use only) |
| Power supply | Internal rechargeable batteries: 8 x NiMH AA 2850 mAh Power adapter: 100...240 V AC input, 9 V DC output External battery pack: 12 V 105 Ah, 25 kg (optional) |
| Operating time | Up to 24 h with fully charged internal batteries |
| Display | LCD graphic display, 128 x 64 dots, backlit |
| Dimensions | 266 (H) x 168 (B) x 37 (T) mm |
| Weight | app. 2 kg |
| Power consumption | <5 W |
| Operating languages | English, French, German, Dutch, Spanish, Italian, Russian, Czech, Turkish, Romanian (others on request) |
Communication
| Interface | RS232, USB cable (optional) |
| Transmitted data | Measured and totalised value, parameter set and configuration, logged data |
KATflow 230 in crush-proof IP 67 transport case
KATflow 230 in operation
Internal data logger
| Storage capacity | app. 30'000 measurements (each comprising up to 10 selectable measurement units), logger size 5 MB app. 100'000 measurements (each comprising up to 10 selectable measurement units), logger size 16 MB (on request) |
| Logged data | All measured and totalised values, parameter sets |
Software KATdata+
| Functionality | Download of measured values/parameter sets, graphical presentation, list format, export to third party software, online transfer of measured data |
| Operating systems | Windows 10, 8, 7, Vista, XP, NT, 2000; Linux |
Quantity and units of measurement
| Volumetric flow rate | m3/h, m3/min, m3/s, l/h, l/min, l/s USGAL/h (US gallons per hour), USGAL/min, USGAL/s bbl/d (barrels per day), bbl/h, bbl/min |
| Flow velocity | m/s, ft/s, inch/s |
| Mass flow rate | g/s, t/h, kg/h, kg/min |
| Volume | m3, l, GAL (US gallons), bbl |
| Mass | g, kg, t |
| Heat flow | W, kW, MW (with heat quantity measurement option) |
| Heat quantity | J, kJ, kW/h (with heat quantity measurement option) |
| Temperature | °C (with heat quantity measurement option) |
Process inputs (galvanically isolated)
| Temperature | PT100 (Clamp-On sensors), three- or four-wire circuit, measurement range: -30...+ 250 °C (-22...+ 482 °F), resolution: 0,1 K, accuracy: ±0,2 K (two or four inputs available) |
Process outputs (galvanically isolated)
| Current | 0/4...20 mA active (RLoad <500 Ω), 16 bit resolution, U = 30 V, accuracy: 0,1 % |
| Digital open-collector | Value: 0,01...1000/unit, width: 1...990 ms, U = 24 V, Imax = 4 mA |
| Digital relay | Form A SPST (NO), U = 48 V, Imax = 250 mA |
Further process outputs available on application.
Transducers
K1L, K1N, K1E
| Pipe diameter range | 50...3000 mm |
| Dimensions of sensor heads | 60 (h) x 30 (w) x 34 (d) mm |
| Material of sensor heads | Stainless steel |
| Material of cable conduits | Type K1L: PVC Type K1N/E: Stainless steel |
| Temperature range | Type K1L: -30...+ 80 °C (-22...+ 176 °F) Type K1N: -30...+ 130 °C (-22...+ 266 °F) Type K1E: -30...+ 250 °C (-22...+ 482 °F) (for short periods up to + 300 °C (+ 572°F)) |
| Degree of protection | IP 66 according to EN 60529 (IP 67 and IP 68 on request) |
| Standard cable lengths | Type K1L: 5 m Type K1N/E: 4 m |
K1N/E transducers
K1L transducers
K1N/E transducers with ODU/LEMO connector
K4L, K4N, K4E
| Pipe diameter range | 10...250 mm for type K4N/E 10...250 mm for type K4L |
| Dimensions of sensor heads | 43 (h) x 18 (w) x 22 (d) mm |
| Material of sensor heads | Stainless steel |
| Material of cable conduits | Type K4L: PVC Type K4N/E: Stainless steel |
| Temperature range | Type K4L: -30...+ 80 °C (-22...+ 176 °F) Type K4N: -30...+ 130 °C (-22...+ 266 °F) Type K4E: -30...+ 250 °C (-22...+ 482 °F) (for short periods up to + 300 °C (+ 572 °F)) |
| Degree of protection | IP 66 according to EN 60529 (IP 67 and IP 68 on request) |
| Standard cable lengths | Type K4L: 5 m Type K4N/E: 2,5 m |
K4N/E transducers
K4L transducers
K4N/E transducers with ODU/LEMO connector
Transducer mounting accessories
General
| Diameter range and mounting types | Clamping set (metal strap with screw), stainless steel: DN 10...40 Clips and chains, chain length 1 m, stainless steel: DN 15...310 Clips and chains, chain length 2 m, stainless steel: DN 25...600 Clips and chains, chain length 4 m (2 x 2 m), stainless steel: DN 25...1200 |
Mounting clip and chains for use with portable flowmeter
Mounting clip
Transducers mounted using chains and clips
General
| Diameter range and mounting types | Mounting fixture, rail and magnets (for type K4 ): DN 10...250 Mounting fixture, rail and magnets (for type K1 ): DN 50...3000 |
| Mounting fixture for flexible hoses | Custom made mounting bracket, stainless steel (available on request) |
Mounting fixture, rail and magnets
Mounting fixture, rail and magnets
Example of mounting fixture for flexible hoses
PT100 Clamp-On sensors
General
| Type | PT100 (Clamp-On sensors) |
| Measurement range | -30...+ 250 °C (-22...+ 482 °F) |
| Circuits | 4-wire |
| Accuracy T | ±(0,15 °C + 2 x 10-3 x T [°C]), class A |
| Accuracy ∆T | ≤ 0,1 K (3 K < ∆T < 6 K) corresponding to EN 1434-1 |
| Response time | 50 s |
| Dimensions of sensor heads | 20 (h) x 15 (w) x 15 (d) mm |
| Material of sensor heads | Aluminium |
| Material of cable jacket | PTFE |
| Cable length | 3 m |
PT100 transducer
PT100 transducer fixed to pipe
KATflow 230 with PT100 transducer
Wall thickness gauges (optional)
Wall thickness gauge NT
| Temperature range | -20...+ 100 °C (-4...+ 212 °F) |
| Measuring range | 1...200 mm |
| Resolution | 0,01 mm |
| Linearity | 0,1 mm |
| Cable length | 1,5 m |
Wall thickness gauge HT
| Temperature range | 0...+ 500 °C (32...+ 932 °F) |
| Measuring range | 1...200 mm |
| Resolution | 0,01 mm |
| Linearity | 0,1 mm |
| Cable length | 1,5 m |
Wall thickness gauge NT
Wall thickness gauge NT in use
Wall thickness gauge HT in use
Transport accessories
Crush-proof transport case
| Dimensions (external) | 190 (h) x 480 (w) x 385 (d) mm |
| Weight (empty) | 3,71 kg |
| Degree of protection | IP 67 according to EN 60529 |
| Outside material | Polypropylene/resin compound |
| Inside material | High-density polyurethane foam |
Soft transport case
| Dimensions (external) | 175 (h) x 450 (w) x 320 (d) mm |
| Weight (empty) | 750 g |
| Degree of protection | No IP rating |
| Outside material | Nylon |
| Inside material | Nylon |
Crush-proof IP 67 transport case
KATflow 230 soft transport case